MP1536-001-20
Circuit Breakers
CIRCUIT BREAKER
MP1536-001-20
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
0.750 inches nominal
-
Trip Release Ambient Temp Rating
-54.0 deg celsius minimum all locations and 71.0 deg celsius maximum all locations
-
Reset Method
manual
-
Body Height
1.900 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Manual Actuator Type And Quantity
1 push button
-
Special Features
terminals seperated by barriers; amper rating marked on actuator
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Body Style
multipole-single actuator type
-
Inclosure Protection Type For Which Designed
shock resistant and vibrationproof
-
Main Contact Tripping Mechanism Type
trip free
-
Terminal Type And Quantity
6 screw
-
Operating Voltage Type And Rating Per Pole In Volts
205.0 ac all locations
-
Frequency In Hertz
400.0 all locations
-
Nominal Thread Size
0.469 inches
-
Thread Series Designator
uns
-
Case Material
plastic
-
Trip Release Method
thermal all locations
-
Actuator Function
reset
-
Trip Release Characteristic
instantaneous all locations
-
Bushing Length
0.250 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Tolerance Class
2b external
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
160.0 all locations
-
Actuator Position Designation
at pole two
-
Ultimate Trip Time Per Pole In Seconds
0.350 minimum all locations and 1.400 maximum all locations