CD6-A2A3A3A3A3A3-DU-W-25-120/240
Circuit Breakers
CIRCUIT BREAKER
CD6-A2A3A3A3A3A3-DU-W-25-120/240
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
5.844 inches nominal
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Body Width
6.192 inches nominal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Surface To Terminal End Distance
2.609 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant and corrosion resistant and shock resistant and humidity resistant and vibration resistant
-
Unthreaded Mounting Hole Diameter
0.156 inches nominal
-
Thread Quantity Per Inch
32
-
Body Style
multipole-multiple actuator type
-
Pole Quantity
6
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.032 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.546 inches nominal
-
Nominal Thread Size
0.138 inches
-
Special Features
barrier,0.120 in. h,on left side
-
Main Contact Tripping Mechanism Type
trip free
-
External Actuator Linkage Arrangement
one, two, three, four, five, and six linked
-
Mounting Facility Type And Quantity
12 threaded stud and 12 unthreaded hole
-
Terminal Type And Quantity
12 threaded stud
-
Boss Height
0.218 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches minimum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.032 inches nominal
-
Manual Actuator Type And Quantity
6 toggle
-
Trip Delay Time In Seconds Per Rated Continuous Current
40.000 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations
-
Case Material
plastic
-
Trip Release Method
magnetic all locations