3XAM17-15-120-55
Circuit Breakers
CIRCUIT BREAKER
3XAM17-15-120-55
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
mica
-
Manual Actuator Type And Quantity
3 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Mounting Surface To Terminal End Distance
2.000 inches nominal
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Length
1.190 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Body Length
2.500 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct all locations and 8.500 maximum at 200 pct all locations
-
Terminal Type And Quantity
6 screw
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Frequency In Hertz
400.0 all locations
-
Precious Material And Location
terminal surfaces silver
-
Test Data Document
26512-gc885r drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Reset Method
manual
-
Precious Material
silver
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Body Width
2.273 inches nominal