B30D0038-115
Circuit Breakers
CIRCUIT BREAKER
B30D0038-115
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
4a single pole type
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
1.875 inches maximum
-
Pole Quantity
1
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Trip Release Method
magnetic-hydraulic single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
~1
stant and salt spray proof
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and humidity resistant and moisture resi
-
Unpackaged Unit Weight
2.500 ounces
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.550 inches minimum and 1.570 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.650 inches minimum and 1.670 inches maximum
-
Arc Quenching Method
magnetic blowout
-
Terminal Type And Quantity
2 tab w/screw
-
Thread Series Designator
unc
-
Frequency In Hertz
50.0 or 60.0
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.200 minimum at 200 pct and 20.000 maximum at 200 pct single location
-
Actuator Position Designation
at pole one
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Trip Release Characteristic
time delay single location
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Special Handling Feature
magnetic
-
Mounting Facility Type And Quantity
2 threaded hole