1241C54G01
Circuit Breakers
CIRCUIT BREAKER
1241C54G01
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
12.750 inches nominal
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud
-
Switch Current Rating And Type In Amps
5.0 ac and 5.0 dc
-
Body Width
9.000 inches maximum
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Switch Location And Position Designation
internal at pole three
-
Reset Method
manual
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Switch Terminal Type
tab, solder lug
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct all locations and 32.000 maximum at 200 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations
-
Mounting Surface To Terminal End Distance
10.375 inches nominal
-
Inclosure Protection Type For Which Designed
general purpose
-
Boss Height
0.125 inches nominal
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.000 inches nominal
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Body Style
multipole-single actuator type
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
14.625 inches nominal
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Switch Contact Arrangement
single pole, double throw
-
Actuator Position Designation
at pole two
-
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
-
Trip Release Method
thermal-magnetic all locations
-
Center To Center Distance Between Terminals Parallel To Width
3.000 inches nominal
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Body Length
15.500 inches maximum