W91X15-3-1
Circuit Breakers
CIRCUIT BREAKER
W91X15-3-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct single location and 1.500 maximum at 200 pct single location and 0.030 minimum at 400 pct single location and 0.250 maximum at 400 pct single location
-
Maximum Continuous Load Current Rating Per Pole
1.0 amperes dc single location
-
Thread Series Designator
unc
-
Reset Method
manual
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
2 threaded hole
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc single location
-
Pole Quantity
1
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Body Style
single pole type
-
Trip Release Method
magnetic-hydraulic single location
-
Ultimate Trip Time Per Pole In Seconds
7.000 maximum single location
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc single location
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant