W92X11-2-25
Circuit Breakers
CIRCUIT BREAKER
W92X11-2-25
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Body Style
8c multipole-multiple actuator type
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Body Width
2.490 inches minimum and 2.510 inches maximum
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Arc Quenching Method
magnetic blowout
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
Terminal Type And Quantity
4 threaded stud
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
dustproof
-
Frequency In Hertz
60.0
-
Thread Series Designator
unc