804785-11
Circuit Breakers
CIRCUIT BREAKER
804785-11
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic-hydraulic single location
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Fragility Factor
moderately rugged
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location
-
Thread Series Designator
unc
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.030 minimum at 400 pct single location and 1.500 maximum at 200 pct single location and 0.150 minimum at 200 pct single location and 0.200 maximum at 400 pct single location
-
Reset Method
manual
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac single location
-
Body Style
single pole type
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Frequency In Hertz
50.0 single location or 60.0 single location
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip single location
-
Manual Actuator Type And Quantity
1 toggle
-
Pole Quantity
1
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Surface To Terminal End Distance
2.611 inches nominal
-
Circuit Protection Type
overcurrent single location
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Mounting Facility Type And Quantity
2 threaded hole
-
Ultimate Trip Time Per Pole In Seconds
0.700 minimum single location
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Actuator Position Designation
at pole one
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum