ETN2753
Circuit Breakers
CIRCUIT BREAKER
ETN2753
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
6 quick disconnect, male
-
Center To Center Distance Between Terminals Parallel To Width
1.344 inches nominal
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Boss Height
0.188 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Actuator Position Designation
at pole two
-
Trip Delay Time In Seconds Per Rated Continuous Current
5.000 minimum at 200 pct all locations and 15.000 maximum at 200 pct all locations
-
Body Height
4.062 inches nominal
-
Trip Release Method
thermal-magnetic all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.938 inches nominal
-
Arc Quenching Method
air
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Body Length
6.500 inches nominal
-
Reset Method
manual
-
Body Width
4.125 inches nominal
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Special Handling Feature
magnetic
-
Fragility Factor
moderately rugged
-
~1
data on certain environmental and performanc
-
Test Data Document
81349-mil-c-17361 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.827 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.688 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes ac all locations
-
Unthreaded Mounting Hole Diameter
0.190 inches nominal
-
Special Features
circuit breaker supplied with two threaded metal inserts
-
Frequency In Hertz
400.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations
-
Specification/Standard Data
81349-mil-c-17361/4 government specification