AM3R-Z29-102
Circuit Breakers
CIRCUIT BREAKER
AM3R-Z29-102
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Reset Method
manual
-
Features Provided
sliding bar interlock
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.030 minimum at 400 pct all locations and 0.150 minimum at 200 pct all locations and 1.500 maximum at 200 pct all locations and 0.200 maximum at 400 pct all locations
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Mounting Facility Type And Quantity
6 threaded hole
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Body Width
2.240 inches minimum and 2.251 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Manual Actuator Type And Quantity
3 toggle
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Ultimate Trip Time Per Pole In Seconds
0.700 minimum all locations
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum