13221E8302-1

Circuit Breakers

CIRCUIT BREAKER

13221E8302-1

5925-01-139-6337

5925 - Circuit Breakers

Cecom Lr Center

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    130.0 all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    208.0 ac all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Width

    1.026 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Arc Quenching Method

    air

  • Body Style

    multipole-multiple actuator type

  • Trip Delay Time In Seconds Per Rated Continuous Current

    11.000 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Body Width

    3.078 inches nominal

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Body Height

    2.609 inches nominal

  • Body Length

    5.800 inches nominal

  • Boss Height

    0.219 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Manual Actuator Type And Quantity

    3 toggle

  • External Actuator Linkage Arrangement

    one and two linked

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...