APL111-4613-46

Circuit Breakers

CIRCUIT BREAKER

APL111-4613-46

5925-01-142-0335

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Width

    2.250 inches maximum

  • Fragility Factor

    moderately rugged

  • Maximum Continuous Load Current Rating Per Pole

    100.0 milliamperes ac third location

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    10.500 minimum at 200 pct second location and 60.000 maximum at 200 pct second location

  • Thread Series Designator

    unc

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Release Characteristic

    time delay second location

  • Frequency In Hertz

    60.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Trip Release Characteristic

    time delay first location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic all locations

  • Mounting Surface To Terminal End Distance

    2.151 inches maximum

  • Inclosure Protection Type For Which Designed

    vibration resistant and shock resistant

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.050 inches minimum and 2.070 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Internal Trip Release Configuration

    series trip all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Boss Height

    0.150 inches nominal

  • Reset Method

    manual

  • Actuator Position Designation

    at each pole

  • Terminal Type And Quantity

    6 threaded stud

  • Trip Release Characteristic

    instantaneous third location

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac second location

  • Case Material

    plastic

  • Unpackaged Unit Weight

    11.100 ounces

  • Features Provided

    high inrush protection

  • Manual Actuator Type And Quantity

    3 toggle

  • Trip Delay Time In Seconds Per Rated Continuous Current

    10.500 minimum at 200 pct first location and 60.000 maximum at 200 pct first location

  • Body Length

    2.480 inches minimum and 2.500 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac first location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...