CD4-Z71-1

Circuit Breakers

CIRCUIT BREAKER

CD4-Z71-1

5925-01-146-1292

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct first location and 10.500 maximum at 200 pct first location

  • Center To Center Distance Between Terminals Parallel To Length

    3.546 inches nominal

  • Nominal Thread Size

    0.138 inches

  • Trip Release Characteristic

    time delay second location

  • Switch Current Rating And Type In Amps

    10.0 ac and 4.0 dc

  • Operating Voltage Type And Rating Per Pole In Volts

    36.0 dc fourth location

  • Internal Trip Release Configuration

    series trip third location

  • Frequency In Hertz

    400.0 second location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Trip Release Characteristic

    time delay third location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct third location and 10.500 maximum at 200 pct third location

  • Mounting Facility Type And Quantity

    8 threaded hole and 8 slot

  • Trip Release Characteristic

    instantaneous fourth location

  • Boss Height

    0.218 inches nominal

  • Unpackaged Unit Weight

    2.438 pounds

  • Switch Location And Position Designation

    internal at pole four

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac third location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac first location

  • Maximum Continuous Load Current Rating Per Pole

    60.0 amperes ac first location

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.750 inches nominal

  • Mounting Slot Width

    0.164 inches nominal

  • Frequency In Hertz

    400.0 third location

  • Switch Terminal Type

    quick disconnect, male

  • Terminal Type And Quantity

    8 screw

  • Manual Actuator Type And Quantity

    4 toggle

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.032 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    60.0 amperes ac second location

  • Case Material

    plastic

  • Pole Quantity

    4

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Internal Trip Release Configuration

    series trip first location

  • Trip Release Characteristic

    time delay first location

  • External Actuator Linkage Arrangement

    one, two, three, and four linked

  • Switch Contact Arrangement

    single pole, double throw

  • Test Data Document

    80063-sm-a-838519 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Internal Trip Release Configuration

    series trip second location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac third location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct second location and 10.500 maximum at 200 pct second location

  • Body Length

    5.844 inches nominal

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations and 5000.0 dc all locations

  • Internal Trip Release Configuration

    series trip w/auxiliary load terminal fourth location

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Frequency In Hertz

    400.0 first location

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Body Width

    3.096 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac second location

  • Mounting Surface To Terminal End Distance

    2.609 inches nominal

  • Thread Quantity Per Inch

    32

  • Center To Center Distance Between Terminals Parallel To Width

    1.032 inches nominal

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...