127-0349
Circuit Breakers
CIRCUIT BREAKER
127-0349
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
8.0 amperes ac second location
-
Body Length
1.990 inches minimum and 2.010 inches maximum
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Frequency In Hertz
50.0 second location or 60.0 second location
-
Reset Method
manual
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc first location
-
External Actuator Linkage Arrangement
one and two linked
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac second location
-
Center To Center Distance Between Terminals Parallel To Length
1.550 inches minimum and 1.570 inches maximum
-
Case Material
plastic
-
Internal Trip Release Configuration
series trip w/auxiliary load terminal first location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac second location
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Boss Height
0.120 inches minimum and 0.140 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.650 inches minimum and 1.670 inches maximum
-
Trip Release Characteristic
instantaneous first location
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc first location
-
Terminal Type And Quantity
7 tab, solder lug
-
Mounting Surface To Terminal End Distance
2.200 inches minimum and 2.220 inches maximum
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Body Width
1.490 inches minimum and 1.510 inches maximum
-
Trip Release Characteristic
time delay second location
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc first location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct second location and 0.950 maximum at 200 pct second location
-
Fragility Factor
moderately rugged
-
Circuit Protection Type
overcurrent all locations
-
Internal Trip Release Configuration
relay trip second location
-
Pole Quantity
2