AP16-2R-7331-1
Circuit Breakers
CIRCUIT BREAKER
AP16-2R-7331-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes dc second location
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Pole Quantity
2
-
Maximum Continuous Load Current Rating Per Pole
0.6 amperes ac first location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac first location
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc second location
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Time Per Pole In Seconds
4.000 minimum and 40.000 maximum second location
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 minimum at 125 pct and 40.000 maximum at 125 pct and 0.850 minimum at 200 pct and 4.000 maximum at 200 pct and 0.001 minimum at 400 pct and 0.500 maximum at 400 pct and 0.005 minimum at 800 pct and 0.035 maximum at 800 pct second location
-
Frequency In Hertz
400.0 first location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Ultimate Trip Time Per Pole In Seconds
6.000 minimum and 50.000 maximum first location
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
6.000 minimum at 125 pct and 50.000 maximum at 125 pct and 0.900 minimum at 200 pct and 4.000 maximum at 200 pct and 0.010 minimum at 400 pct and 0.090 maximum at 400 pct and 0.004 minimum at 800 pct and 0.018 maximum at 800 pct first location