APL11-1REC4-20102-2
Circuit Breakers
CIRCUIT BREAKER
APL11-1REC4-20102-2
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Switch Current Rating And Type In Amps
10.0 ac and 3.0 dc
-
Switch Contact Arrangement
single pole, double throw
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 first location
-
Body Style
multipole-multiple actuator type
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
4 threaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.700 minimum at 200 pct all locations and 10.000 maximum at 200 pct all locations
-
Thread Series Designator
unc
-
Pole Quantity
2
-
Circuit Protection Type
overcurrent all locations
-
Special Handling Feature
magnetic
-
Switch Terminal Type
tab, solder lug
-
Fragility Factor
moderately rugged
-
Auxiliary Switch Function And Quantity
1 alarm
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes dc first location
-
Body Width
1.515 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Special Features
pole two is remote trip application
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof and corrosion resistant and moisture resistant and fungus resistant
-
Arc Quenching Method
magnetic blowout
-
Trip Release Method
magnetic-hydraulic first location
-
Main Contact Tripping Mechanism Type
trip free
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc first location
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Case Material
plastic
-
Switch Location And Position Designation
internal at pole one
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Body Length
2.480 inches minimum and 2.520 inches maximum
-
External Actuator Linkage Arrangement
one and two linked
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
120.0 second location
-
Terminal Type And Quantity
4 threaded stud
-
Unpackaged Unit Weight
7.400 ounces
-
Operating Voltage Type And Rating Per Pole In Volts
24.0 dc second location
-
Mounting Surface To Terminal End Distance
2.399 inches minimum and 2.543 inches maximum