JA4-A3-A-30-2
Circuit Breakers
CIRCUIT BREAKER
JA4-A3-A-30-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Mounting Facility Type And Quantity
8 threaded hole
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Thread Quantity Per Inch
32
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Length
1.555 inches minimum and 1.565 inches maximum
-
Reset Method
manual
-
Mounting Surface To Terminal End Distance
1.835 inches minimum and 1.845 inches maximum
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Unpackaged Unit Weight
10.000 ounces
-
Circuit Protection Type
overcurrent all locations
-
Special Handling Feature
magnetic
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations
-
Fragility Factor
moderately rugged
-
Pole Quantity
4
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.745 inches minimum and 0.755 inches maximum
-
Manual Actuator Type And Quantity
4 toggle
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.655 inches minimum and 1.665 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.745 inches minimum and 0.755 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Body Width
2.245 inches minimum and 2.255 inches maximum
-
Nominal Thread Size
0.138 inches
-
Boss Height
0.125 inches minimum and 0.135 inches maximum
-
Terminal Type And Quantity
8 tab, solder lug
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
External Actuator Linkage Arrangement
one, two, three, and four linked
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations