219-4-20141-1
Circuit Breakers
CIRCUIT BREAKER
219-4-20141-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Pole Quantity
4
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Circuit Protection Type
overcurrent third location
-
Internal Trip Release Configuration
series trip first location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac second location
-
Trip Release Characteristic
time delay first location
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac second location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Mounting Slot Width
0.164 inches nominal
-
Manual Actuator Type And Quantity
4 toggle
-
External Actuator Linkage Arrangement
one, two, three, and four linked
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Terminal Type And Quantity
8 threaded stud
-
Internal Trip Release Configuration
series trip second location
-
Center To Center Distance Between Terminals Parallel To Length
3.546 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.032 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac third location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay second location
-
Internal Trip Release Configuration
series trip third location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac first location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 first location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Trip Release Characteristic
time delay third location
-
Mounting Facility Type And Quantity
8 threaded hole and 8 slot
-
Trip Release Characteristic
instantaneous fourth location
-
Boss Height
0.218 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 second location
-
Internal Trip Release Configuration
shunt trip fourth location
-
Unpackaged Unit Weight
2.700 pounds
-
Frequency In Hertz
400.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac first location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 third location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location
-
Body Length
5.844 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 dc fourth location
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac third location
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac third location
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac first location
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct third location and 100.000 maximum at 200 pct third location
-
Body Width
4.128 inches nominal
-
Circuit Protection Type
overcurrent first location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
2.609 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct second location and 100.000 maximum at 200 pct second location
-
Circuit Protection Type
overcurrent second location
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct first location and 100.000 maximum at 200 pct first location
-
Thread Quantity Per Inch
32
-
Center To Center Distance Between Terminals Parallel To Width
1.032 inches nominal
-
Circuit Protection Type
undervoltage fourth location