MIL-C-39019/2

Circuit Breakers

CIRCUIT BREAKER

MIL-C-39019/2

5925-01-167-3317

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Test Data Document

    81349-mil-c-39019 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

  • ~1

    data on certain environmental and performanc

  • Fragility Factor

    moderately rugged

  • Trip Release Method

    magnetic single location

  • Terminal Type And Quantity

    2 wire hook

  • Switch Terminal Type

    tab, solder lug

  • Special Handling Feature

    magnetic

  • Bushing Length

    0.332 inches minimum and 0.380 inches maximum

  • Reset Method

    manual

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Center To Center Distance Between Terminals Parallel To Length

    0.875 inches minimum and 0.906 inches maximum

  • Inclosure Protection Type For Which Designed

    fungus resistant and hermetically sealed

  • Nominal Thread Size

    0.375 inches

  • Thread Quantity Per Inch

    32

  • Body Length

    1.531 inches minimum and 1.562 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Body Width

    0.594 inches minimum and 0.625 inches maximum

  • Switch Location And Position Designation

    internal at pole one

  • Features Provided

    high inrush protection

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac single location and 50.0 dc single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct single location and 0.950 maximum at 200 pct single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac single location and 500.0 dc single location

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Unpackaged Unit Weight

    50.0 grams

  • Maximum Continuous Load Current Rating Per Pole

    20.0 amperes ac single location and 20.0 amperes dc single location

  • Switch Voltage Rating And Type In Volts

    120.0 ac and 50.0 dc

  • Thread Series Designator

    unef

  • Mounting Surface To Terminal End Distance

    1.669 inches minimum and 1.700 inches maximum

  • Body Style

    single pole type

  • Frequency In Hertz

    400.0 single location

  • Switch Current Rating And Type In Amps

    0.5 ac and 0.5 dc

  • Main Contact Tripping Mechanism Type

    trip free

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Trip Release Characteristic

    time delay single location

  • Specification/Standard Data

    81349-mil-c-39019/2 government specification

  • Internal Trip Release Configuration

    series trip single location

  • Manual Actuator Type And Quantity

    1 toggle

  • Case Material

    metal

  • Pole Quantity

    1

  • Switch Contact Arrangement

    single pole, double throw

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...