AP114-7480-1

Circuit Breakers

CIRCUIT BREAKER

AP114-7480-1

5925-01-170-2272

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.950 maximum at 200 pct second location

  • Nominal Thread Size

    0.375 inches

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 dc third location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Mounting Surface To Terminal End Distance

    1.780 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    500.0 milliamperes ac first location

  • Trip Release Characteristic

    time delay first location

  • Terminal Type And Quantity

    4 wire hook

  • Center To Center Distance Between Terminals Parallel To Length

    0.875 inches nominal

  • Special Features

    pole three is a switch

  • Body Style

    multipole-single actuator type

  • Case Material

    metal

  • Manual Actuator Type And Quantity

    1 toggle

  • Maximum Continuous Load Current Rating Per Pole

    500.0 milliamperes ac second location

  • Trip Release Characteristic

    time delay second location

  • Frequency In Hertz

    60.0 first location or 60.0 second location or 400.0 second location

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac first location

  • Actuator Position Designation

    between pole one and two

  • Main Contact Tripping Mechanism Type

    trip free

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Reset Method

    manual

  • Frequency In Hertz

    400.0 first location

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.625 inches nominal

  • Unpackaged Unit Weight

    3.600 ounces

  • Body Length

    1.562 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac first location

  • Operating Voltage Type And Rating Per Pole In Volts

    12.0 dc third location

  • Thread Series Designator

    unef

  • Body Width

    1.281 inches maximum

  • Inclosure Protection Type For Which Designed

    shockproof and hermetically sealed and vibrationproof

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac second location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct first location and 0.055 minimum at 200 pct second location and 0.950 maximum at 200 pct first location

  • Bushing Length

    0.380 inches maximum

  • Trip Release Characteristic

    instantaneous third location

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac second location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...