UPGX-112-7079-1
Circuit Breakers
CIRCUIT BREAKER
UPGX-112-7079-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Body Width
2.260 inches minimum and 2.270 inches maximum
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.735 inches minimum and 0.765 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.515 inches minimum and 1.545 inches maximum
-
Thread Series Designator
unc
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
8 quick disconnect, male
-
Thread Quantity Per Inch
32
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Internal Trip Release Configuration
series/relay trip first location
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Actuator Position Designation
at pole two
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.647 inches minimum and 1.677 inches maximum
-
Mounting Facility Type And Quantity
6 threaded hole
-
Auxiliary Trip Coil Voltage Type And Rating In Volts
250.0 ac nominal first location
-
Trip Release Characteristic
instantaneous first location
-
Internal Trip Release Configuration
series trip second location
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct second location and 20.000 maximum at 200 pct second location
-
Trip Release Characteristic
time delay second location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.735 inches minimum and 0.765 inches maximum
-
Internal Trip Release Configuration
series trip third location
-
Mounting Surface To Terminal End Distance
2.390 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Trip Release Characteristic
time delay third location
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct third location and 20.000 maximum at 200 pct third location
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Inclosure Protection Type For Which Designed
moisture resistant and corrosion resistant and shock resistant and vibration resistant
-
Trip Release Duty Cycle
continuous first location
-
Special Features
rocker actuator attached to circuit breaker handle
-
Bushing Length
0.235 inches minimum and 0.265 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations
-
Case Material
plastic