AM2-A7-A-1.5/3A-3

Circuit Breakers

CIRCUIT BREAKER

AM2-A7-A-1.5/3A-3

5925-01-175-8205

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Boss Height

    0.140 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Iii Storage Type

    general purpose warehouse

  • Iii Special Handling Feature

    magnetic

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Thread Series Designator

    unc

  • Terminal Type And Quantity

    6 threaded stud

  • Mounting Surface To Terminal End Distance

    2.471 inches nominal

  • Body Style

    8c multipole-multiple actuator type

  • Body Length

    2.500 inches nominal

  • Body Width

    1.500 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Iii Fragility Factor

    moderately rugged

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.150 minimum at 200 pct and 1.500 maximum at 200 pct all locations

  • Internal Trip Release Configuration

    series trip w/dual rating all locations

  • External Actuator Linkage Arrangement

    one and two linked

  • Actuator Position Designation

    at each pole

  • Actuator Function

    trip-reset

  • Manual Actuator Type And Quantity

    2 toggle

  • Main Contact Tripping Mechanism Type

    trip free

  • Reset Method

    manual

  • Trip Release Method

    magnetic-hydraulic all locations

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Continuous Load Current Rating Per Pole

    1.5 amperes ac and 3.0 amperes ac all locations

  • Iii Arc Quenching Method

    magnetic blowout

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...