985611-002

Circuit Breakers

CIRCUIT BREAKER

985611-002

5925-01-180-0080

5925 - Circuit Breakers

Titan Corp The

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac third location

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Pole Quantity

    4

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac second location

  • Bushing Length

    0.130 inches nominal

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac first location

  • Frequency In Hertz

    50.0 first location or 60.0 first location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.130 minimum at 200 pct second location and 1.300 maximum at 200 pct second location

  • Manual Actuator Type And Quantity

    2 toggle

  • Center To Center Distance Between Terminals Parallel To Length

    1.530 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac first location

  • External Actuator Linkage Arrangement

    two and three linked

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 fourth location

  • Trip Release Characteristic

    instantaneous fourth location

  • Terminal Type And Quantity

    10 tab w/screw

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 third location

  • Trip Release Characteristic

    time delay third location

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac third location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Operating Voltage Type And Rating Per Pole In Volts

    65.0 dc fourth location

  • Internal Trip Release Configuration

    series trip third location

  • Actuator Position Designation

    at pole two and at pole three

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 second location

  • Trip Release Characteristic

    time delay second location

  • Nominal Thread Size

    0.138 inches

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes dc fourth location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac third location

  • Internal Trip Release Configuration

    series trip second location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.130 minimum at 200 pct first location and 1.300 maximum at 200 pct first location

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Switch Current Rating And Type In Amps

    10.0 ac and 3.0 dc

  • Switch Contact Arrangement

    single pole, double throw

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Trip Release Characteristic

    time delay first location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 first location

  • Internal Trip Release Configuration

    series trip first location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.130 minimum at 200 pct third location and 1.300 maximum at 200 pct third location

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic all locations

  • Mounting Facility Type And Quantity

    8 threaded hole

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.032 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc fourth location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac second location

  • Body Width

    3.015 inches maximum

  • Body Length

    2.000 inches nominal

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Frequency In Hertz

    50.0 third location or 60.0 third location

  • Reset Method

    manual

  • Frequency In Hertz

    50.0 second location or 60.0 second location

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac second location

  • Thread Series Designator

    unc

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.660 inches nominal

  • Circuit Protection Type

    overcurrent all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Switch Terminal Type

    tab, solder lug

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac first location

  • Internal Trip Release Configuration

    relay trip fourth location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...