ETN6726
Circuit Breakers
CIRCUIT BREAKER
ETN6726
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performanc
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Arc Quenching Method
air
-
Body Width
9.000 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 335.0 dc all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Mounting Surface To Terminal End Distance
7.562 inches maximum
-
Reset Method
manual
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Special Handling Feature
magnetic
-
Mounting Facility Type And Quantity
6 unthreaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 all locations
-
Fragility Factor
moderately rugged
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
17.000 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
15.125 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations and 150000.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations and 400.0 amperes dc all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 600 pct all locations and 32.000 maximum at 600 pct all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.000 inches nominal
-
Frequency In Hertz
60.0 all locations
-
Body Length
17.937 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Specification/Standard Data
81349-mil-c-17361 government specification
-
Boss Height
0.250 inches nominal
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Actuator Position Designation
at pole two
-
Trip Release Method
thermal-magnetic all locations
-
Center To Center Distance Between Terminals Parallel To Width
3.000 inches nominal
-
Test Data Document
81349-mil-c-17361 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type