7274-11-2 1/2
Circuit Breakers
CIRCUIT BREAKER
7274-11-2 1/2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
1a single pole type
-
Body Width
0.750 inches nominal
-
Mounting Surface To Terminal End Distance
1.707 inches nominal
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac and 28.0 dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
800.0 ac and 2000.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Function
trip-reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct single location
-
Inclosure Protection Type For Which Designed
shockproof
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Frequency In Hertz
400.0 single location
-
Thread Series Designator
uns
-
Terminal Type And Quantity
2 tab w/screw
-
Bushing Length
0.250 inches nominal
-
Body Length
0.562 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
0.593 inches nominal
-
Iii Fragility Factor
moderately rugged
-
Iii Arc Quenching Method
air
-
Iii Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
2.5 amperes ac and 2.0 amperes dc single location
-
Trip Release Method
thermal single location
-
Trip Release Characteristic
time delay single location
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.469 inches
-
Iii Unpackaged Unit Weight
38.0 grams