209-1-1R-63-4-8-15
Circuit Breakers
CIRCUIT BREAKER
209-1-1R-63-4-8-15
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
1.026 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.547 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Special Handling Feature
magnetic
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location
-
Trip Release Method
magnetic-hydraulic single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
internal at pole one
-
Switch Current Rating And Type In Amps
10.0 ac and 4.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
-
Thread Series Designator
unc
-
Body Style
12a single pole type
-
Mounting Slot Width
0.178 inches nominal
-
Body Length
5.800 inches nominal
-
Case Material
plastic
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Fragility Factor
moderately rugged
-
Boss Height
0.219 inches nominal
-
Mounting Surface To Terminal End Distance
4.871 inches nominal
-
Pole Quantity
1
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole and 1 unthreaded hole and 1 slot
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole one
-
Auxiliary Switch Function And Quantity
1 alarm
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct single location and 32
-
Trip Delay Time In Seconds Per Rated Continuous Current
105.000 maximum at 200 pct single location
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Switch Terminal Type
tab, solder lug
-
Frequency In Hertz
50.0 single location or 60.0
-
Unpackaged Unit Weight
9.000 ounces
-
Terminal Type And Quantity
2 threaded stud