299-4-5055-17
Circuit Breakers
CIRCUIT BREAKER
299-4-5055-17
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
5.125 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
1.026 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.026 inches nominal
-
Mounting Surface To Terminal End Distance
3.550 inches nominal
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 dc
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Circuit Protection Type
overcurrent
-
Actuator Position Designation
at each pole
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.010 minimum at 600 pct and 1.000 maximum at 600 pct
-
Special Features
special construction,not ul listed or recognized
-
Thread Series Designator
unc
-
Body Style
multipole-multiple actuator type
-
Body Width
4.144 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.550 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Fragility Factor
moderately rugged
-
Boss Height
0.220 inches nominal
-
Pole Quantity
4
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
8 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
4 toggle
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one,two,three,and four linked
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
general purpose
-
Frequency In Hertz
400.0
-
Terminal Type And Quantity
8 threaded stud