AM2-B3A3-A-12.5-2-25-2
Circuit Breakers
CIRCUIT BREAKER
AM2-B3A3-A-12.5-2-25-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
4 threaded stud
-
Frequency In Hertz
60.0
-
Inclosure Protection Type For Which Designed
dustproof
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Circuit Protection Type
overcurrent
-
Maximum Continuous Load Current Rating Per Pole
12.5 amperes dc
-
Mounting Facility Type And Quantity
4 threaded hole
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Case Material
plastic
-
Body Width
1.490 inches minimum and 1.510 inches maximum
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Thread Quantity Per Inch
32
-
Storage Type
general purpose warehouse
-
Arc Quenching Method
magnetic blowout
-
Pole Quantity
2
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Thread Series Designator
unc
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 minimum at 200 pct and 8.000 maximum at 200 pct
-
External Actuator Linkage Arrangement
one and two linked
-
Actuator Position Designation
at each pole
-
Manual Actuator Type And Quantity
2 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Trip Release Characteristic
time delay
-
Trip Release Method
magnetic-hydraulic
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac