GH3-Z61-1
Circuit Breakers
CIRCUIT BREAKER
GH3-Z61-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
4 slot
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
relay trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.120 minimum at 200 pct and 0.180 maximum at 200 pct
-
Mounting Slot Width
2.000 inches nominal
-
Body Length
6.000 inches nominal
-
Body Width
4.130 inches nominal
-
Body Height
3.130 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.380 inches nominal
-
Boss Height
0.250 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
5.190 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.880 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.380 inches nominal
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
14000.0 ac
-
Trip Release Method
magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Internal Trip Release Configuration
series trip
-
Inclosure Protection Type For Which Designed
shock resistant
-
Frequency In Hertz
50.0 or b60.0
-
Terminal Type And Quantity
6 compression and 2 wire lead