Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Length

    1.925 inches minimum and 1.955 inches maximum

  • Reset Method

    manual

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Unthreaded Mounting Hole Diameter

    0.151 inches minimum and 0.161 inches maximum

  • Boss Height

    0.135 inches minimum and 0.165 inches maximum

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Center To Center Distance Between Terminals Parallel To Width

    2.487 inches minimum and 2.517 inches maximum

  • Case Material

    metal

  • Body Width

    2.265 inches maximum

  • Main Contact Tripping Mechanism Type

    trip free

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Frequency In Hertz

    50.0 all locations or 60.0 all locations

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.055 inches minimum and 2.065 inches maximum

  • Mounting Surface To Terminal End Distance

    2.506 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    8.000 minimum at 125 pct all locations and 80.000 maximum at 125 pct all locations

  • Manual Actuator Type And Quantity

    3 toggle

  • Mounting Facility Type And Quantity

    6 unthreaded hole

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.745 inches minimum and 0.755 inches maximum

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...