72-126-17MG6
Circuit Breakers
CIRCUIT BREAKER
72-126-17MG6
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
8c multipole-multiple actuator type
-
Body Width
2.230 inches minimum and 2.270 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.925 inches minimum and 1.955 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.735 inches minimum and 0.765 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.047 inches minimum and 2.077 inches maximum
-
Mounting Facility Type And Quantity
6 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct and 10.000 maximum at 200 pct all locations
-
Frequency In Hertz
400.0
-
Unpackaged Unit Weight
0.875 pounds
-
Test Data Document
05869-711570 drawing
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Body Length
2.485 inches minimum and 2.515 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.735 inches minimum and 0.765 inches maximum
-
Fragility Factor
moderately rugged
-
Boss Height
0.125 inches minimum and 0.155 inches maximum
-
Mounting Surface To Terminal End Distance
2.475 inches minimum and 2.505 inches maximum
-
Pole Quantity
3
-
Arc Quenching Method
magnetic blowout
-
Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one, two, and three linked
-
~1
oof
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and moisture resistant and salt spray pr