CC3200
Circuit Breakers
CIRCUIT BREAKER
CC3200
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
4.750 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Body Style
multipole-single actuator type
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Body Height
3.203 inches nominal
-
Boss Height
0.125 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
200.0 amperes ac all locations
-
Case Material
plastic
-
Unthreaded Mounting Hole Diameter
0.187 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Body Length
6.125 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Width
4.125 inches nominal
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
150.000 minimum at 200 pct all locations and 600.000 maximum at 200 pct all locations
-
Trip Release Characteristic
time delay all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches nominal