Technical Characteristics
-
Body Length
16.000 inches nominal
-
Special Features
includes flux transfer shunt trip,rated 32 vdc,120 vac,60 hz
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 45.000 maximum at 200 pct all locations
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Precious Material And Location
contacts silver
-
Reset Method
manual
-
Adjustable Trip Setting Current Range Per Pole In Amps
+4000.0/+8000.0 ac all locations
-
Unthreaded Mounting Hole Diameter
0.344 inches nominal
-
Precious Material
silver
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Boss Height
0.938 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Body Width
8.250 inches nominal
-
Frequency In Hertz
63.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
22000.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
14.375 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Height
4.062 inches nominal
-
Features Provided
adjustable trip release and interchangeable trip release
-
Actuator Position Designation
at pole two
-
Maximum Continuous Load Current Rating Per Pole
800.0 amperes ac all locations
-
Body Style
multipole-single actuator type
-
Inclosure Protection Type For Which Designed
fungus resistant and corrosion resistant and shock resistant and vibration resistant
-
Manual Actuator Type And Quantity
1 toggle
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
11.500 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Case Material
plastic