WC375/19-007
Circuit Breakers
CIRCUIT BREAKER
WC375/19-007
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Specification/Standard Data
81348-w-c-375/19 government specification
-
Terminal Type And Quantity
2 screw
-
Thread Series Designator
unc
-
Frequency In Hertz
60.0
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 maximum at 200 pct single location
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Characteristic
time delay single location
-
Trip Release Method
thermal-magnetic single location
-
Circuit Protection Type
overcurrent single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Special Handling Feature
magnetic
-
Storage Type
general purpose warehouse
-
Mounting Facility Type And Quantity
2 threaded hole
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
4.380 inches nominal
-
Case Material
plastic
-
Body Height
4.560 inches nominal
-
Body Length
5.434 inches nominal
-
Body Style
8a single pole type
-
Test Data Document
81348-w-c-375 specification
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Inclosure Protection Type For Which Designed
corrosion resistant
-
Nominal Thread Size
0.138 inches
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Manual Actuator Type And Quantity
1 toggle
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac single location
-
Thread Quantity Per Inch
32
-
Pole Quantity
1
-
Body Width
1.026 inches nominal