AM2-Z159-12
Circuit Breakers
CIRCUIT BREAKER
AM2-Z159-12
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Trip Release Characteristic
instantaneous second location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct all locations and 11.000 maximum at 200 pct all locations
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Terminal Type And Quantity
4 threaded stud
-
External Actuator Linkage Arrangement
one and two linked
-
Body Length
2.480 inches minimum and 2.520 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Features Provided
high inrush protection
-
Case Material
plastic
-
Special Features
high inrush pole one only
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
3.590 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc all locations
-
Body Width
1.480 inches minimum and 1.520 inches maximum
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Operating Voltage Type And Rating Per Pole In Volts
35.0 dc second location
-
Pole Quantity
2
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Unpackaged Unit Weight
6.438 pounds
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Trip Release Characteristic
time delay first location
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc first location
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc first location
-
Test Data Document
80063-sm-a-838525 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Arc Quenching Method
magnetic blowout