Technical Characteristics

  • Body Style

    caaql 15b

  • Body Width

    4.125 inches nominal

  • Body Height

    3.875 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.656 inches nominal

  • Switch Contact Arrangement

    single pole, double throw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    2.750 inches nominal

  • Boss Height

    0.188 inches nominal

  • Pole Quantity

    3

  • Features Provided

    adjustable trip release

  • Operating Voltage Type And Rating Per Pole In Volts

    500.0 ac and 250.0 dc .

  • Trip Release Characteristic

    instantaneous and time delay .

  • Actuator Function

    trip-reset

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Adjustable Trip Setting Current Range Per Pole In Amps

    +900.0/+1050.0 ac and +900.0/+1050.0 dc .

  • Switch Location And Position Designation

    internal at pole three

  • Inclosure Protection Type For Which Designed

    general purpose

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal .

  • Switch Terminal Type

    wire lead

  • Switch Current Rating And Type In Amps

    15.0 ac and 0.5 dc

  • Switch Voltage Rating And Type In Volts

    460.0 ac and 125.0 dc

  • Body Length

    6.500 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    3.938 inches nominal

  • Mounting Facility Type And Quantity

    2 unthreaded hole

  • Maximum Continuous Load Current Rating Per Pole

    75.0 amperes ac and 75.0 amperes dc .

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac and 15000.0 dc .

  • Circuit Protection Type

    overcurrent .

  • Trip Release Method

    thermal-magnetic .

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 600 pct and 32.000 maximum at 600 pct .

  • Frequency In Hertz

    60.0

  • Terminal Type And Quantity

    6 quick disconnect, female

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...