ETN275310
Circuit Breakers
CIRCUIT BREAKER
ETN275310
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
caaql 15b
-
Body Width
4.125 inches nominal
-
Body Height
3.875 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Unthreaded Mounting Hole Diameter
0.190 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.656 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 inches nominal
-
Boss Height
0.188 inches nominal
-
Pole Quantity
3
-
Features Provided
adjustable trip release
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac and 250.0 dc .
-
Trip Release Characteristic
instantaneous and time delay .
-
Actuator Function
trip-reset
-
Auxiliary Switch Function And Quantity
1 alarm
-
Adjustable Trip Setting Current Range Per Pole In Amps
+900.0/+1050.0 ac and +900.0/+1050.0 dc .
-
Switch Location And Position Designation
internal at pole three
-
Inclosure Protection Type For Which Designed
general purpose
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal .
-
Switch Terminal Type
wire lead
-
Switch Current Rating And Type In Amps
15.0 ac and 0.5 dc
-
Switch Voltage Rating And Type In Volts
460.0 ac and 125.0 dc
-
Body Length
6.500 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
3.938 inches nominal
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes ac and 75.0 amperes dc .
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac and 15000.0 dc .
-
Circuit Protection Type
overcurrent .
-
Trip Release Method
thermal-magnetic .
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 600 pct and 32.000 maximum at 600 pct .
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
6 quick disconnect, female