6364-1-90
Circuit Breakers
CIRCUIT BREAKER
6364-1-90
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
3b multipole-single actuator type
-
Body Length
2.203 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.437 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.781 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Mounting Surface To Terminal End Distance
2.031 inches nominal
-
Arc Quenching Method
air
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
600.0 ac and 600.0 dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
thermal all locations
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Nominal Thread Size
0.164 inches
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Thread Series Designator
unc
-
Terminal Type And Quantity
4 screw
-
Frequency In Hertz
60.0
-
Inclosure Protection Type For Which Designed
dustproof
-
Trip Delay Time In Seconds Per Rated Continuous Current
595.000 nominal at 200 pct all locations
-
Internal Trip Release Configuration
series trip all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac and 30.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
90.0 amperes ac and 90.0 amperes dc all locations
-
Mounting Facility Type And Quantity
4 threaded hole
-
Pole Quantity
2
-
Fragility Factor
moderately rugged
-
Case Material
plastic
-
Body Width
1.546 inches nominal