TQC2130WL
Circuit Breakers
CIRCUIT BREAKER
TQC2130WL
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 all locations
-
External Actuator Linkage Arrangement
one and two linked
-
Terminal Type And Quantity
2 clip and 2 compression
-
Case Material
plastic
-
Trip Release Method
thermal all locations
-
Inclosure Protection Type For Which Designed
general purpose
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Manual Actuator Type And Quantity
2 toggle
-
Body Width
2.000 inches nominal
-
Mounting Facility Type And Quantity
4 terminal
-
Body Length
3.875 inches nominal
-
Fragility Factor
moderately rugged
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 dc all locations
-
Body Height
2.359 inches nominal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
18.000 minimum at 200 pct all locations and 125.000 maximum at 200 pct all locations
-
Internal Trip Release Configuration
series trip all locations
-
Body Style
multipole-multiple actuator type
-
Boss Height
0.187 inches nominal
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free