T11-2-3.00A-02-20A
Circuit Breakers
CIRCUIT BREAKER
T11-2-3.00A-02-20A
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
50.0 single location or 60.0 single location
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes dc single location
-
Body Width
0.680 inches nominal
-
Terminal Type And Quantity
2 tab, solder lug
-
Body Style
single pole type
-
Mounting Facility Type And Quantity
1 threaded stud
-
Thread Series Designator
un
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location and 50.0 dc single location
-
Case Material
plastic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 single location
-
Bushing Length
0.468 inches nominal
-
Pole Quantity
1
-
Mounting Surface To Terminal End Distance
1.555 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.125 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
~1
single location and 0.008 minimum at 600 pct sin
-
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 maximum at 200 pct single location and 0.100 minimum at 400 pct single location and 4.000 maximum at 400 pct single location and 2.000 maximum at 600 pct single location and 70.000 maximum at 135 pct single location and 3.000 minimum at 135 pct
-
Trip Release Method
magnetic single location
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Reset Method
manual
-
Nominal Thread Size
0.500 inches
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location and 1000.0 dc single location
-
Actuator Function
trip-reset
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Body Length
1.375 inches nominal