AM2-B3A3-A-P1-15A-65VDC-2/P2-15A
Circuit Breakers
CIRCUIT BREAKER
AM2-B3A3-A-P1-15A-65VDC-2/P2-15A
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac second location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc first location
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one and two linked
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 22.000 maximum at 200 pct second location
-
Frequency In Hertz
60.0 second location
-
Thread Series Designator
unc
-
Thread Pitch Diameters
0.1177 to 0.1214 inches
-
Body Width
1.515 inches minimum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
0.745 inches minimum and 0.755 inches maximum
-
Boss Height
0.135 inches minimum and 0.165 inches maximum
-
Body Style
8c multipole-multiple actuator type
-
Body Length
2.480 inches minimum and 2.500 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.930 inches minimum and 1.950 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.045 inches minimum and 2.075 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.735 inches minimum and 0.765 inches maximum
-
Iii Fragility Factor
moderately rugged
-
Pole Quantity
2
-
Iii Arc Quenching Method
magnetic blowout
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac second location
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes dc first location
-
Mounting Surface To Terminal End Distance
2.797 inches minimum and 2.827 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Iii Storage Type
general purpose warehouse
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc first location
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.650 minimum at 200 pct and 10.000 maximum at 200 pct first location
-
Inclosure Protection Type For Which Designed
dustproof
-
Terminal Type And Quantity
4 threaded stud