AM2S-D3-LA-02-D-A-60-2

Circuit Breakers

CIRCUIT BREAKER

AM2S-D3-LA-02-D-A-60-2

5925-01-285-2047

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct all locations and 18.000 maximum at 200 pct all locations

  • Fragility Factor

    moderately rugged

  • Body Width

    1.480 inches minimum and 1.520 inches maximum

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Unpackaged Unit Weight

    6.500 ounces

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Boss Height

    0.120 inches minimum and 0.160 inches maximum

  • Mounting Surface To Terminal End Distance

    2.441 inches minimum and 2.521 inches maximum

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Inclosure Protection Type For Which Designed

    shock resistant and moisture resistant and fungus resistant and humidity resistant and vibration resistant

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations and 5000.0 dc all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Center To Center Distance Between Terminals Parallel To Width

    0.730 inches minimum and 0.770 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    60.0 amperes ac all locations and 60.0 amperes dc all locations

  • Manual Actuator Type And Quantity

    2 toggle

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations and 65.0 dc all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.918 inches minimum and 1.958 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.730 inches minimum and 0.770 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.042 inches minimum and 2.082 inches maximum

  • Terminal Type And Quantity

    4 threaded stud

  • External Actuator Linkage Arrangement

    one and two linked

  • Body Length

    2.480 inches minimum and 2.520 inches maximum

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...