ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Fragility Factor

    moderately rugged

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    2 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • Nominal Thread Size

    0.138 inches

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    4 threaded stud

  • Body Style

    8c multipole-multiple actuator type

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Method

    magnetic-hydraulic all locations

  • External Actuator Linkage Arrangement

    one and two linked

  • Internal Trip Release Configuration

    series trip all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct all locations and 60.000 maximum at 200 pct

  • Thread Series Designator

    unc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.