HJD3100

Circuit Breakers

CIRCUIT BREAKER

HJD3100

5925-01-301-9773

5925 - Circuit Breakers

Eaton Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    25000.0 ac all locations and 22000.0 dc all locations

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Main Contact Tripping Mechanism Type

    trip free

  • Terminal Type And Quantity

    6 compression

  • Frequency In Hertz

    60.0 all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Boss Height

    0.250 inches nominal

  • Body Style

    multipole-single actuator type

  • Actuator Position Designation

    at pole two

  • Body Height

    4.062 inches nominal

  • Trip Release Method

    thermal-magnetic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Center To Center Distance Between Terminals Parallel To Length

    8.094 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.250 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    7.250 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    100.0 amperes ac all locations and 100.0 amperes dc all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations and 250.0 dc all locations

  • Body Length

    10.000 inches nominal

  • Actuator Function

    trip-reset

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Storage Type

    general purpose warehouse

  • Features Provided

    adjustable trip release

  • Reset Method

    manual

  • Body Width

    4.125 inches nominal

  • Adjustable Trip Setting Current Range Per Pole In Amps

    +500.0/+1000.0 ac all locations and +500.0/+1000.0 dc all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Trip Release Characteristic

    instantaneous all locations

  • Fragility Factor

    moderately rugged

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...