3179574-21
Circuit Breakers
CIRCUIT BREAKER
3179574-21
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Body Length
1.562 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
4.0 amperes ac all locations
-
Frequency In Hertz
400.0 all locations
-
Switch Terminal Type
pin
-
Nonturn Device Diameter
0.180 inches minimum and 0.300 inches maximum
-
Thread Series Designator
unef
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and fungus resistant and moisture resistant and salt spray proof
-
Auxiliary Switch Function And Quantity
1 alarm
-
Center To Center Distance Between Terminals Parallel To Width
0.687 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.200 minimum at 200 pct all locations and 6.000 maximum at 200 pct all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Bushing Length
0.280 inches minimum and 0.380 inches maximum
-
Test Data Document
10001-3179574 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Pole Quantity
2
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Switch Location And Position Designation
internal at pole two
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
1.828 inches maximum
-
Internal Trip Release Configuration
series trip all locations
-
Nonturn Device Location
at 12 oclock
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Terminal Type And Quantity
4 wire hook
-
Switch Contact Arrangement
single pole, double throw
-
Body Style
multipole-single actuator type
-
Nonturn Device Radius
0.625 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Body Width