UPGN1122269
Circuit Breakers
CIRCUIT BREAKER
UPGN1122269
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Mounting Surface To Terminal End Distance
2.200 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Bushing Length
0.495 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 125 pct all locations and 120.000 maximum at 125 pct all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations
-
Terminal Type And Quantity
4 quick disconnect, male
-
Body Width
1.500 inches nominal
-
Nominal Thread Size
0.500 inches and 0.138 inches
-
Thread Series Designator
un and unc
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal and 2 threaded hole
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Ultimate Trip Time Per Pole In Seconds
120.000 nominal all locations
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Inclosure Protection Type For Which Designed
waterproof