44-7-S-H-N-160A
Circuit Breakers
CIRCUIT BREAKER
44-7-S-H-N-160A
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Frequency In Hertz
60.0 single location
-
Terminal Type And Quantity
2 tab w/screw
-
Overall Height
1.580 inches nominal
-
Case Material
plastic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 single location
-
Fragility Factor
moderately rugged
-
Body Style
rectangular dimensional envelope
-
Trip Release Ambient Temp Rating
70.0 deg fahrenheit nominal single location
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
30.000 minimum at 200 pct single location and 180.000 maximum at 200 pct single location
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Manual Actuator Type And Quantity
1 push button
-
Circuit Protection Type
overcurrent single location
-
Overall Width
5.000 inches nominal
-
Overall Length
6.690 inches nominal
-
Pole Quantity
1
-
Operating Voltage Type And Rating Per Pole In Volts
400.0 ac single location and 28.0 dc single location
-
Trip Release Method
thermal-magnetic single location
-
Unpackaged Unit Weight
30.000 ounces
-
Trip Release Characteristic
time delay single location
-
Inclosure Protection Type For Which Designed
corrosion resistant and shock resistant and humidity resistant and fungus proof and vibration resistant
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
4000.0 ac single location and 10000.0 dc single location
-
Maximum Continuous Load Current Rating Per Pole
160.0 amperes ac single location and 160.0 amperes dc single location
-
Mounting Facility Type And Quantity
2 terminal