0032469-001

Circuit Breakers

CIRCUIT BREAKER

0032469-001

5925-01-324-4110

5925 - Circuit Breakers

Harris Technical Services Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Mounting Surface To Terminal End Distance

    2.471 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    41.0 amperes ac first location

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Method

    magnetic all locations

  • Auxiliary Trip Coil Voltage Type And Rating In Volts

    115.0 ac nominal third location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Manual Actuator Type And Quantity

    3 toggle

  • Actuator Function

    trip-reset

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Internal Trip Release Configuration

    series trip first location

  • Internal Trip Release Configuration

    series trip second location

  • Nominal Thread Size

    0.138 inches

  • Trip Release Duty Cycle

    continuous third location

  • Switch Location And Position Designation

    external at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct all locations and 80.000 maximum at 200 pct

  • Switch Terminal Type

    tab, solder lug

  • Switch Current Rating And Type In Amps

    10.0 ac and 4.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Terminal Type And Quantity

    7 threaded stud

  • Body Style

    8c multipole-multiple actuator type

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Body Width

    2.240 inches minimum and 2.260 inches maximum

  • Switch Contact Arrangement

    single pole, double throw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Storage Type

    general purpose warehouse

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    22.5 amperes ac third location

  • Maximum Continuous Load Current Rating Per Pole

    40.0 amperes ac second location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Characteristic

    time delay all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Actuator Position Designation

    at each pole

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip w/remote trip feature third location

  • Inclosure Protection Type For Which Designed

    moisture resistant and salt water resistant and humidity resistant

  • Frequency In Hertz

    50.0 all locations or 60.0

  • Thread Series Designator

    unc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...