841398-6
Circuit Breakers
CIRCUIT BREAKER
841398-6
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
21.000 minimum at 200 pct first location and 100.000 maximum at 200 pct first location
-
Maximum Continuous Load Current Rating Per Pole
100.0 milliamperes ac third location
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Slot Width
0.154 inches minimum and 0.174 inches maximum
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.016 inches minimum and 1.036 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
21.000 minimum at 200 pct second location and 100.000 maximum at 200 pct second location
-
Boss Height
0.209 inches minimum and 0.229 inches maximum
-
Thread Quantity Per Inch
32
-
Mounting Surface To Terminal End Distance
3.475 inches minimum and 3.495 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc first location
-
Trip Release Method
magnetic-hydraulic all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc second location
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes dc first location
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and moisture resistant and salt spray proof
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes dc second location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay second location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and 2.760 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
1.016 inches minimum and 1.036 inches maximum
-
Frequency In Hertz
60.0 third location
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac third location
-
Operating Voltage Type And Rating Per Pole In Volts
140.0 dc first location
-
Mounting Facility Type And Quantity
6 threaded hole and 3 slot
-
Manual Actuator Type And Quantity
3 toggle
-
Operating Voltage Type And Rating Per Pole In Volts
140.0 dc second location
-
Body Width
3.108 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac third location
-
Case Material
plastic
-
Trip Release Characteristic
instantaneous third location
-
Terminal Type And Quantity
6 threaded stud
-
Body Length
4.740 inches minimum and 4.760 inches maximum
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.537 inches minimum and 3.557 inches maximum
-
Trip Release Characteristic
time delay first location