12931847
Circuit Breakers
CIRCUIT BREAKER
12931847
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic single location
-
Reset Method
manual
-
Nominal Thread Size
0.500 inches
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Body Width
0.750 inches nominal
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc single location
-
Switch Contact Arrangement
single pole, double throw
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Bushing Length
0.625 inches nominal
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc single location
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Mounting Surface To Terminal End Distance
2.232 inches maximum
-
Body Style
single pole type
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct single location and 10.000 maximum at 200 pct single location
-
Thread Series Designator
unef
-
Terminal Type And Quantity
2 tab w/screw
-
Auxiliary Switch Function And Quantity
1 alarm
-
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc single location
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic